C O N D U I T I N S TA L L AT I O N A P P L I C AT I O N S
Conduit spacing best practices:
•
Increase conduit separations at larger sites, especially on longer parallel cable runs.
•
If possible, maintain at least 12" (30.5 cm) of separation between low and high
voltage cable routed in underground conduits in well-tamped earth.
•
When separation is breached to crossover conduits, they must cross at 90° to
avoid parallel low and high voltage cable routing.