FIELD WIRING CABLE: S E L E C T I O N G U I D E
Use the following visual reference for cable selection when field wiring common
Franklin Electric probes, sensors, and other equipment.
PROBES: FMP-LL3, TSP-LL2
DISCRIMINATING MAG SENSOR: TSP-DMS
VAPOR FLOW METER: TS-VFM
VAPOR PRESSURE SENSOR: TS-VPS
ELLD TRANSDUCER: LSU500-U, LSU500**, LSU500E**
FMP-XXX-U UNIVERSAL DEVICE PROTOCOL SENSORS:
DTS-U, DDS-U, DDS-UD, EIS-U, DIS-U, HIS-U, HIS-XL-U, CDS-U, and DPS-U
Belden™ 89182 2-Wire, Twisted
pair, 1500' (457 m) Max cable
length
Belden™ 8760 2-Wire, Twisted
pair, 1000' (304m) Max cable
length
Belden™ 88761/ 87761 2-Wire,
Twisted pair, 400' (120 m) Max
cable length
Belden™ 87760/88760 2-Wire,
Twisted pair, 260'(79 m) Max
cable length
AlphaWire 58113 3-Wire,
1500' (457 m) Max cable length
Belden™ 8770 3-Wire, Multi pair,
1500' (457 m) Max cable length
Type THHN, TFFN, or THWN Gas
& Oil Resistant, 18 AWG minimum
1500' (457 m) Max cable length
Belden™ 7962A 4-Wire, Quad
(2 Pair), 600' (182 m) Max cable
length
*Applies to the TSP-XXX versions of these sensors.
**The LSU500 and LSU500E transducers may use any cable marked below at lengths of up to 1,500'.