GUARDIAN SPGC-220 SMART CONTROLLER: D I P S W I T C H O P T I O N S
POLE
DESCRIPTION
FUNCTION
1
Fault Shutdown
When this is ON, an abnormal condition detected
on any controller in a Primary-Secondary or AC
configuration causes all connected controllers to
shut down.
2
Unused
The default position is ON.
3
PrimarySecondary
ON designates the SPGC-220 as the Primary
controller. This switch must be set to OFF for
Secondary and Stand-Alone configurations.
4
AC
When the Primary controller is ON, the AC feature
is active. OFF indicates a Secondary or Stand-Alone
configuration.
5
Extended Run
Disable
ON disables the extended run feature.
OFF activates the extended run feature.
6
DEF Mode
ON enables use with Diesel Exhaust Fluid submersible
(for models DEF-PMA150A or DEF-PMA150B only).*
7
Unused
8
Unused
O 1 2 3 4 5 6 7 8
N
SW2:
SW2
Unused switch. The default position is OFF.
POLE
DESCRIPTION
1
Address 0
2
Address 1
3
Address 2
4
Address 3
FUNCTION
Use poles 1-5 to set the addressing switches for
Primary-Secondary or AC configurations.
5
Address 4
6
Fault Readout
ON activates the fault readout function.
7
Bypass
ON bypasses diagnostics for 10 minutes.
8
Auto Restart
When ON, the controller tries to restart the STP in an
underload (UL) fault condition.
*DEF Mode is available only with SPGC-220 revision 0.3.8 firmware or higher.
(The firmware revision is shown when the controller starts up and resets.)