MAGVFC™/ ECOVFC™ VARIABLE SPEED CONTROLLER: DIP S WITC H SETTINGS
SW6 & SW3 OPTIONS:
DESCRIPTION
8
Not used
7
Not used
6
Not used
5
Proportional Alternating (see manual)
4
Timed Alternating (see manual)
3
IST-VFC
ON: Communication with IST-VFC active
OFF: Communication with MagVFC™ or EcoVFC™ active
2
FAULT SHUTDOWN
ON: All pumps disabled if one is in alarm
OFF: Only the pump in alarm is disabled
1
EXTEND RUN
ON: Extended run disabled | OFF: Extended run active
SW3
DESCRIPTION
8
ALTERNATING CIRCUIT
ON: Primary controller only | OFF: No Alternating or Secondary
7
AUTOMATIC RESTART
ON: Controller will reset UL alarm when hook applied
OFF: Manual reset of UL alarm required
6
PMA HORSE POWER
ON: VS4 | OFF: VS2
5
Pipe compensation (see manual)
4
Pipe compensation (see manual)
3
ON: Primary-Secondary or Primary-Secondary Alternating
OFF: Stand-Alone Secondary
2
ON: Gasoline products | OFF: Diesel products
1
MLD VS. PLLD
ON: 6 second PSI increase to 34 PSI (for MLD or LS500 ELLD)
OFF: 8 PSI increase for 6 seconds (for Veeder-Root™ PLLD)