FFS-1040 EVO Series Complete Guide Interactive - Flipbook - Page 19
C
B
F
D
E
A
ACCESSORIES:
SENSORS
No matter the application, whether it’s dispenser sumps, turbine
sumps, tank interstitial spaces, or specialty setups, the EVO™ Series
offers a full range of compatible containment monitoring solutions to
meet the site’s requirements.
SENSOR TYPES:
A
Liquid Sensors
C
Discriminating Sensors
A discriminating sensor detects the presence of
both fuel and water, distinguishing between the
two. It’s typically placed in a containment area to
alert operators of leaks, helping ensure quick and
accurate response to specific liquid types.
E
D
Interstitial Sensors
An interstitial sensor is placed in the space between
a double-walled fuel tank or pipe to detect leaks.
It alerts operators if fuel or liquid enters this
area, signaling a potential breach in the primary
containment, helping prevent environmental
contamination.
Multiplexing Sensor Hub™
The Multiplexing Sensor Hub™ (MSH) allows station
owners to add additional sensors to existing sites
without having to break concrete to run new conduit
and wires. The MSH typically uses existing cabling
to power and connect up to six total devices to an
EVO™ console.
These sensors utilize water and product floats to
detect the presence of water or hydrocarbons and
also alert when the sensor installation has been
tampered with. Sensors report water and product
alarms, including a programmable high water limit.
Based on float-switch technology and made of
chemically-resistant materials, the liquid sensor
can be installed in containments, basins, double
wall tanks or other locations where the presence of
liquid indicates a leak has occurred.
B
Magnetostrictive “Mag” Sensors
F
Corrosion Detection Sensor
The Corrosion Control™ Corrosion Detection
Sensor provides proactive, automated alerts when
corrosive conditions are present in the tank ullage
space. This helps prevent corrosion that can lead
to fuel system deterioration. Installed directly in
the ullage space, the sensor uses a replaceable
sacrificial metal screen to detect early signs of
corrosion before damage occurs.
19