2025 UL Ordering Catalog - Flipbook - Page 245
SPECIFICATIONS
Operating Temperature
-40° to 140° F (-40° to 60° C)
Storage Temperature
-40° to 158° F (-40° to 70° C)
Accuracy
+/-0.040" (1.0 mm) / +/- 1.0° C
Repeatability
±0.001" / +/- 0.03° C
Resolution
+/- 0.001" (0.025 mm) / +/- 0.01° C
Temperature Sensors
5 thermistors located in the shaft
Probe Cable
10' long three conductor cables with shields
and polyurethane jacket
EVO™ Series Console
Compatibility
EVO™ Series, TS-5, TS-550, TS-5000,
Colibri®, TS-1001/2011/750/504/508
Fuel Compatibility
Diesel with or without biodiesel blends up
to 5% (B5), diesel with biodiesel blends
between 6% - 20% (B6 - B20), diesel with
biodiesel blends between 97% - 100%
(B99 - B100), gasoline with ethanol blends
up to 10% (E10), mid-range ethanol/
gasoline blends of (E15-20), high-range
ethanol/gasoline blends (E51-83)
commercially sold as E85
Operation
An electromagnetic field is created inside the probe head and forms around
a long waveguide within the probe shaft when position measurements are
taken. The electromagnetic field interacts with the magnetic field of the
float(s) and produces a shock wave in the waveguide that travels at a known
speed. When the shock wave is detected at the probe head, the probe
creates a signal that corresponds precisely to the product level. Product
expansion calculations are enabled by temperature sensors that are located
at various points in the probe shaft.
Minimum Detectable Water Level
Minimum Detectable
Water Level
Float Type
Approvals/
Certifications
UL & cUL listed, ATEX, IECEx
TSP-IGF4 / TSP-IGFD3 Gasoline Floats
0.75" (1.91 cm)
TSP-IDF4 / TSP-IGF4D3 Diesel Floats
0.75" (1.91 cm)
TSP-IGF4P Phase Separation Float
0.44" (1.12 cm)
FMP-IDF4E Low Level Water for Diesel Float
0.25" (0.64 cm)
Applications
• The leak detection probes are typically used for underground
storage tanks and petroleum applications when static or SCALD®
leak detection is required.
• The inventory control probes are typically used for aboveground
storage tanks, chemical or oil waste, or underground storage
tanks that do not require in-tank leak detection.
Components
• Probe head
2• Guides
3• Bottom mount fitting
4• Probe shaft
5• 2" or 4" gas or diesel product float (sold as kit with water float)
6• 2" or 4" gas or diesel water floats (sold as kit with product float)
7• Phase separation float kit
8• Low level water float kit for diesel
9• LPG float
10• Chemical float
2
1
1
FUEL MANAGEMENT
SYSTEMS
2
5
Note: All float kits sold separately.
7
4
8
6
3
9
Digital Inventory & Leak Detection Probes
10
245