S940 SENSOR ALARM CONSOLE
ORDERING INFORMATION
SPECIFICATIONS
Model
Description
Input channels
4 (2-wire float switch sensor inputs)
S940
Four channel sensor alarm console
Output channels
2 (dry contact relay outputs)
Alarm
Internal audible alarm
LEDs
Alarm, power, and output LEDs
Compatible
Franklin Fueling
Systems 2-wire
sensors
−
−
−
−
Dimensions
6" × 6" × 4"
Power
requirements
100-240 VAC +/- 10%, 50/60 Hz, 15 W max
Operating
temperaure
-13° F to +140° F (-25° C to +60° C)
Enclosure
NEMA® 4, indoor / outdoor
(non-hazardous locations only)
−
Capabilities
Approvals /
Certifications
TSP-ULS universal liquid sensor
TSP-HLS high level sensor
TSP-HFS horizontal float switch
TSP-UHS universal hydrostatic sensor
Tank overfill alarm
−
Steel or fiberglass tank interstitial monitoring
−
Containment sump monitoring
−
General liquid sensor monitoring
−
Programmable relay outputs for remote alarm
or external device interface
−
UL, cUL, associated apparatus,
non-hazardous location
Third party certification of leak
detection capabilities
−