2025 UL Ordering Catalog - Flipbook - Page 231
SECONDARY CONTAINMENT MONITORING
ORDERING INFORMATION
Secondary Containment Control Modules
Accessories
Model
Description
Model
Description
TS-SCCM/1
Single channel secondary containment control module
TSP-SCBRB
¼" NPT barbed fittings (Qty 5)
TS-SCCM/2
Dual channel secondary containment control module
TSP-SCBRBT
¼" NPT barbed T-fitting
TS-SCMCAL
Leak generator kit, one per station
TSP-SCCLP
Hose clamps (Qty 5)
VS-SCCM/1
220 VAC single channel secondary containment
control module
TSP-SCTB25
25' vacuum hose
TSP-SCTB50
50' vacuum hose
VS-SCCM/2
220 VAC dual channel secondary containment
control module
TSP-SCTB100
100' vacuum hose
TSP-SCVLV
Schrader valves (Qty 5)
400137937
Syphon check valve
Installation Kits
TSP-SCVLV-PF Push-Fit stem to Barb fitting (Qty 5)
Model
Description
TSP-SCLSI
Product, vapor line and sump containment install kit
TSP-SCTK2
Tank containment install kit for 2" NPT risers*
TSP-SCTK2B
Tank containment install kit for 2" BSP risers*,
TSP-SCTK4
Tank containment install kit for 4" NPT risers*
TSP-SCTK4B
Tank containment install kit for 4" BSP risers*,
1
8
2
5
*In-tank hose sold separately
3
4
SPECIFICATIONS
6
Components
Secondary containment control module
2
Vacuum line to secondary contained pipe
3
Pipe fitting with integrated test port
4
Secondary contained pipe
5
Vacuum line to secondary contained tank
Operation
6
Tank installation kit
7
Line weight (included with tank install kit)
8
Syphon check valve
9
EVOTM 550/5000 or EVOTM 600/6000
with SCM software*
Secondary containment monitoring uses the syphon port of the submersible
turbine pump to draw and maintain a vacuum on the secondary
containments of lines, sumps, tanks and vapor lines. During installation a
calibrated leak is introduced during the AUTO-LEARN® process which
allows the system to learn the vacuum characteristics of each containment
space. The vacuum level is continuously monitored and compared to
established leak rates to ensure that the secondary containment is tight.
FUEL MANAGEMENT
SYSTEMS
1
9
7
Operating
vacuum level
-2 to -6 in Hg
Software
Available software option on EVO™ 550,
EVO™ 5000, EVO™ 600, and EVO™ 6000
−
Requirements
−
−
TS-420IB, TS-RLY and TS-ACI Modules and the
TS-SCM software option must
be ordered and installed in the EVO™
Requires TS-SCCM secondary containment
control module consisting of pressure sensor(s)
and solenoid valve(s)
Requires syphon check valve to connect
to STP manifold
Secondary Containment Monitoring
Containments
Containments to be monitored must
terminate inside the submersible turbine
pump containment
Vacuum
limitation
Installer must verify the vacuum limitation of
each containment with its manufacturer prior
to installation
Approvals /
Certifications
−
−
Meets all requirements of California AB2481
National Work Group approved
231