2025 UL Ordering Catalog - Flipbook - Page 229
EVO™ SERIES ELECTRONIC LINE LEAK DETECTION
ORDERING INFORMATION
Site Requirements
EVO™ Series Electronic Line Leak Detection Kits
• EVO™ 600/6000
Model
Description
• TS-ELLD software option (TS-ELLD-G software option for
generator-specific applications)
FMP-LS500/1
1-line ELLD kit, includes (1) pressure transducer, (1)
leak generator kit (TS-ALCAL), (1) needle valve kit
(TS-ALNIP)
FMP-LS500/2
2-line ELLD kit, includes (2) pressure transducer, (1)
leak generator kit (TS-ALCAL), (2) needle valve kit
(TS-ALNIP)
FMP-LS500/3
3-line ELLD kit, includes (3) pressure transducer, (1)
leak generator kit (TS-ALCAL), (3) needle valve kit
(TS-ALNIP)
FMP-LS500/4
4-line ELLD kit, includes (4) pressure transducer, (1)
leak generator kit (TS-ALCAL), (4) needle valve kit
(TS-ALNIP)
• TS-ACI, TS-420IB, *TS-RLY Modules
* TS-RLY Module is not required when utilizing Turbine Pump Interface™ (TPI)
communications. Franklin Electric intelligent pump controllers required for TPI.
2
1
3
5:15 PM
Line 1
Unleaded
Control
Enabled
Idle
Idle
Done
Line Status
Pump Status
Test Status
Learn Status
Last Test
Gross Test
Monthly Test
Annual Test
Passed
Passed
Passed
5/31/2023 9:07 AM
5/30/2023 1:05 AM
5/30/2023 6:05 AM
All systems normal
FMP-LSU500
Replacement pressure transducer
TS-ALCAL
Leak generator kit
TS-ALNIP
Needle valve kit for standard fuels
TS-AFALNIP
Needle valve kit for E85 fuel
SPECIFICATIONS
Operation
Pressure Transducer
™
1• The EVO Pressure Transducer is typically installed in the leak detector
2• During non-pumping periods, the EVO™ will conduct line leak testing by
comparing the line pressure changes to those learned during the
AUTO-LEARN® process. A deviation in pressure, such as a drop beyond
predefined thresholds, will be declared as a leak and shut down the
associated submersible pump.
3• With declaration of a leak, the system will notify the operator via the
EVO™ display with additional email or SMS notification through the FFS
PRO® Connect Web Browser Interface.
Line Volume Requirements - Gross Test
Pipework System
Dimensions
4" × 2" NPT
Operating temperature
-40° F to 149° F (-40° C to 66° C)
Operating pressure
0 to 100 psi (0 to 689 kPa)
Sensor port fitting
2" female NPT
Sensor material
Anodized aluminum body and
stainless steel sensor
Approvals / Certifications
−
−
FUEL MANAGEMENT
SYSTEMS
port of the submersible pump manifold. During the AUTO-LEARN®
setup process, EVO™ learns the pressure decay curve characteristics of
a calibrated leak.
UL, cUL, ATEX, IECEx
Third party certification of leak
detection capabilities
Minimum Pressure Requirements
Gallons
Liters
Rigid / hybrid (rigid + flexible)*
2.5 – 1202.02
9.5 – 2359.1
UPP® pipework (semi-rigid)
2.5 – 623.2
9.5 – 1185.5
APT® XP pipework (flexible)
2.5 – 313.17
9.5 – 4550.1
Item
Value
15 psi (1.034 bar) for gross 3.0 gph (11.4 lph) hourly tests
Minimum
Pump Off
Pressure
17.5 psi (1.207 bar) for monthly 0.2 gph (0.8 lph) precision tests
22.5 psi (1.551 bar) for annual 0.1 gph (0.4 lph)precision tests
20 psi (1.379 bar) for learning lines
Line Volume Requirements - Precision Test
Pipework System
Gallons
Liters
Rigid / hybrid (rigid + flexible)**
2.5 – 559.02
9.5 – 2116.1
UPP® pipework (semi-rigid)
2.5 – 161.46
9.5 – 611.2
APT® XP pipework (flexible)
2.5 – 81.19
9.5 – 307.3
EVO™ Series Electronic Line Leak Detection
* To be considered hybrid, the bulk modulus of the line must be at a minimum of
20,000 psi for gross tests.
* *To be considered hybrid, the bulk modulus of the line must be at a minimum of
35,000 psi for precision tests.
229