2025 EN Catalog-Interactive - Flipbook - Page 91
SPECIFICATIONS (CONT.)
Pressure Transducer
Dimensions
4" x 2" NPT
Operating temperature
-40° F to 149° F (-40° C to 66° C)
Operating pressure
0 to 100 psi (0 to 689 kPa)
Sensor port fitting
2" female NPT
Sensor material
Anodized aluminum body and stainless steel sensor
Approvals & Certifications
–
UL, cUL, ATEX, IECEx
–
Third party certification of leak detection capabilities
Minimum Pressure Requirements
Value
Minimum Pump Off Pressure
– 15 psi (1.034 bar) for gross 3.0 gph (11.4 lph) hourly tests
– 17.5 psi (1.207 bar) for monthly 0.2 gph (0.8 lph) precision tests
– 22.5 psi (1.551 bar) for annual 0.1 gph (0.4 lph) precision tests
– 20 psi (1.379 bar) for learning lines
FUEL MANAGEMENT
SYSTEMS
Item
Line Volume Requirements - Gross Test
Pipework System
Gallons
Liters
Rigid / hybrid (rigid + flexible)*
2.5 - 1202.02
9.5 - 2359.1
UPP® pipework (semi-rigid)
2.5 - 623.2
9.5 - 1185.5
APT® XP pipework (flexible)
2.5 - 313.17
9.5 - 4550.1
Line Volume Requirements - Gross & Precision Test
Pipework System
Gallons
Liters
Rigid / hybrid (rigid + flexible)*
2.5 - 559.02
9.5 - 2116.1
UPP® pipework (semi-rigid)
2.5 - 161.46
9.5 - 611.2
APT® XP pipework (flexible)
2.5 - 81.19
9.5 - 4550.1
ORDERING INFORMATION
Site Requirements
• EVO™ 600/6000
• TS-ELLD software options (TS-ELLD-G software option for generator-specific applications)
• TS-ACI, TS-420IB, *TS-RLY Modules
* TS-RLY Module is not required when utilizing Turbine Pump Interface™ (TPI) communications. Franklin Electric intelligent pump controllers required for TPI.
EVO™ Series Electronic Line Leak Detection Kits
Model
Description
FMP-LS500/1
1-line ELLD kit, includes (1) pressure transducer, (1) leak generator kit (TS-ALCAL), (1) needle valve kit (TS-ALNIP)
FMP-LS500/2
2-line ELLD kit, includes (2) pressure transducer, (1) leak generator kit (TS-ALCAL), (2) needle valve kit (TS-ALNIP)
FMP-LS500/3
3-line ELLD kit, includes (3) pressure transducer, (1) leak generator kit (TS-ALCAL), (3) needle valve kit (TS-ALNIP)
FMP-LS500/4
4-line ELLD kit, includes (4) pressure transducer, (1) leak generator kit (TS-ALCAL), (4) needle valve kit (TS-ALNIP)
FMP-LSU500
Replacement pressure transducer
TS-ALCAL
Leak generator kit
TS-ALNIP
Needle valve kit for standard fuels
TS-AFALNIP
Needle valve kit for E85 fuel
91