2025 EN Catalog-Interactive - Flipbook - Page 17
MULTIPLEXING
SENSOR HUB™
CORROSION CONTROL
The Multiplexing Sensor Hub™ (MSH) allows you to use a
single 4-wire cable to connect up to six devices to an EVO™
600 or EVO™ 6000 automatic tank gauge (EVO™ console).
HIGHLIGHTS
• For retrofit applications: the MSH can use existing 4-wire
probe and sensor cables to add additional probes or
sensors, providing expanded monitoring capabilities
without the need to break concrete to run additional cable.
• For new applications: the MSH delivers labor and materials
savings by reducing the amount of conduit and cable
required for monitoring devices within a containment
sump.
• Ideal for use in adding a Corrosion Control™ Water
Separator and corrosion detection sensors (FMP-CDS-U)
to an existing tank sump and provides all necessary input
capabilities for this system.
SPECIFICATIONS
Inputs
Output to
EVO™600/6000
Connections
Type of
connections
Approvals &
Certifications
• Six input channels provide a wide assortment of device
communication capabilities:
• Channel 1: Always on, for FMP-LL3 digital inventory
and leak detection probes.
• Channel 2-5: Multiplexed, for 2-wire universal device
protocol (UDP) communication devices.
• Channel 5: Additional capability for 2-wire devices.
• Channel 6: For any dry-contact single pole single throw
(SPST) switch, a flow switch, two-wire device, or
temperature sensor based on a 10k thermistor.
Input Capabilities
The FMP-MSH is capable of supporting the following devices:
(1) LL3 probe, (4) UDP devices,
(1) switch/temperature sensor
(1) RS-485
The FMP-MSH requires a minimum of
four wires connected directly to an
EVO™ 600 with an RS485 module
Power, ground, A, and B communication
for the RS485 module. If a sump has
two input field cables that are both
2-conductor cables, the A and B
connections should be wired in the same
cable that must be a twisted pair.
Power and ground should be on the other
cable. If it is a new installation, Belden™
cable #7962A, or a cable with equivalent
parameters, is recommended. The
FMP-MSH can power and accept input
from 6 different probes or sensors.
UL listed, ATEX/IECEx
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
FMP-LL3
FMP-DDS-U
FMP-DDS-U
FMP-DDS-U
FMP-DDS-U
FMP-ULS
--
FMP-DTS-U
FMP-DTS-U
FMP-DTS-U
FMP-DTS-U
FMP-UHS
--
FMP-EIS-U
FMP-EIS-U
FMP-EIS-U
FMP-EIS-U
FMP-HFS2
--
FMP-DIS-U
FMP-DIS-U
FMP-DIS-U
FMP-DIS-U
10k Temp.
Sensor
--
FMP-HIS-U
FMP-HIS-U
FMP-HIS-U
FMP-HIS-U
--
--
FMP-CDS-U
FMP-CDS-U
FMP-CDS-U
FMP-CDS-U
--
--
FMP-LL3-18*
FMP-LL3-18*
FMP-LL3-18*
FMP-LL3-18*
--
--
--
--
--
FMP-ULS
--
*The FMP-LL3-18 is integrated into the Corrosion Control™ Water Separator to detect
water level in the vessel.
ORDERING INFORMATION
Model
Description
FMP-MSH
Multiplexing Sensor Hub™
Belden™ is a trademark of Belden Technologies, Inc.
SYSTEM
COMPONENTS
Add these Corrosion Control™
System items to your site
to proactively prevent and
detect corrosion.
EVO™ 600 OR
EVO™ 6000
WATER
SEPARATOR
CORROSION
DETECTION SENSOR
DESICCANT
PACK
ADVANCED
PROTECTION STP
17